The NuCAT 5210 F* Hatch allows for the temporary passage of cables from one property to another. In the event of a fire, it ensures the integrity of the fire break in the partition in which it has been installed.
* Also named "Chatière"
Product Data
- The NuCAT 5210 F is made of two metal half-sheaths with an articulated shutter closure and a fireproof lid on each side of the partition
- There are three types of NuCAT 5210 F: 100, 150, 200
- Acts as a fire break for up to two hours (EI 120) (Tested according to the 2004 French decree and the EN 1366–3 standard)
- Installation in a 150 mm thick wall—has the same density as concrete
- Can act as a complete seal if a joint that ensures a physical barrier to smoke and hot gases is added
- Acts as a radiation shield if the lid is specially treated to deflect X- and gamma rays
Operational Information
- The NuCAT 5210 F Hatch is installed differently in a concrete wall or a 150 mm thick slab
- Prepare a borehole for the installation of the NuCAT 5210 F Hatch:
- Type 100 =120 mm borehole
- Type 150 = 170 mm borehole
- Type 200 = 200 mm borehole
Other Technical Information (Packaging, Storage)
- Packaged under a plastic cover
ADDITIONAL INFORMATION
- Acts as a fire break for up to two hours (EI 120) in both concrete slabs and walls (Tested according to the 2004 French decree and the EN 1366–3 standard), with an option for a sealing rating of 2 m TDH (total dynamic head)
System Options (Except for the penetration)
- Protection from one property to another: Air-tight to cold smoke, waterproof
- Radiation protection: The lid is inserted in the NuCAT 5210 F Hatch
References
- 2009: NuCAT 5210 F type 100—Ling’Ao 3 & 4 Nuclear Power Plants (China): One hundred pairs
- 2008: NuCAT 5210 F type 100—EPR Olkiluoto (Finland): Sixteen pairs
- 2007: NuCAT 5210 F type 100—Koeberg Nuclear Power Plant (South Africa): Twenty pairs